Back to the facilities work sheetTRC facilities docs

Electrical loads mapped to panels

Every known electrical load, its room, peak kW and the panel or breaker it is traced to. Rows with no panel are open capture items.

LoadRoomVoltsPeak kWPanelBreakerBasis
Rooftop heat pump #1 (Lounge)roof240 (208-230)3.166roof-hvac inferenceSource: ~/electrical-plan/context/texts-ari-electrical.txt:159 (Greg: an AC 'wired directly into the panel on the roof'); chat.db 937758 (Victor: roof panel 'just for hvac', 7 ACs)unmapped unknownSource: capture #10: Taji's 10/1 AC-to-breaker results (chat.db 944159) not recordedMeasured running kW, energy log AC Unit #1; standby 0.05 kW crankcase/controls is inferred
Rooftop heat pump #2 (Recording Room)roof240 (208-230)3.597roof-hvac inferenceSource: ~/electrical-plan/context/texts-ari-electrical.txt:159 (Greg: an AC 'wired directly into the panel on the roof'); chat.db 937758 (Victor: roof panel 'just for hvac', 7 ACs)unmapped unknownSource: capture #10: Taji's 10/1 AC-to-breaker results (chat.db 944159) not recordedMeasured running kW, energy log AC Unit #2; standby 0.05 kW crankcase/controls is inferred
Rooftop heat pump #3 (Office)roof240 (208-230)3.696roof-hvac inferenceSource: ~/electrical-plan/context/texts-ari-electrical.txt:159 (Greg: an AC 'wired directly into the panel on the roof'); chat.db 937758 (Victor: roof panel 'just for hvac', 7 ACs)unmapped unknownSource: capture #10: Taji's 10/1 AC-to-breaker results (chat.db 944159) not recordedMeasured running kW, energy log AC Unit #3; standby 0.05 kW crankcase/controls is inferred
Rooftop heat pump #4 (Mixing Room (roof doc marks ?))roof240 (208-230)2.157roof-hvac inferenceSource: ~/electrical-plan/context/texts-ari-electrical.txt:159 (Greg: an AC 'wired directly into the panel on the roof'); chat.db 937758 (Victor: roof panel 'just for hvac', 7 ACs)unmapped unknownSource: capture #10: Taji's 10/1 AC-to-breaker results (chat.db 944159) not recordedMeasured running kW, energy log AC Unit #4; standby 0.05 kW crankcase/controls is inferred
Rooftop heat pump #5 (Live Room + iso (AC Pro PKHP-M-0601BB 5-ton))roof240 (208-230)2.983roof-hvac inferenceSource: ~/electrical-plan/context/texts-ari-electrical.txt:159 (Greg: an AC 'wired directly into the panel on the roof'); chat.db 937758 (Victor: roof panel 'just for hvac', 7 ACs)unmapped unknownSource: capture #10: Taji's 10/1 AC-to-breaker results (chat.db 944159) not recordedMeasured running kW, energy log AC Unit #5; standby 0.05 kW crankcase/controls is inferred
Rooftop heat pump #6 (Mezzanine)roof240 (208-230)3.2roof-hvac inferenceSource: ~/electrical-plan/context/texts-ari-electrical.txt:159 (Greg: an AC 'wired directly into the panel on the roof'); chat.db 937758 (Victor: roof panel 'just for hvac', 7 ACs)unmapped unknownSource: capture #10: Taji's 10/1 AC-to-breaker results (chat.db 944159) not recordedNo running reading in the energy log (inrush only); 3.2 kW = median of the five measured units
Rooftop heat pump #7 (Rehearsal Room (roof doc marks ?))roof240 (208-230)3.2roof-hvac inferenceSource: ~/electrical-plan/context/texts-ari-electrical.txt:159 (Greg: an AC 'wired directly into the panel on the roof'); chat.db 937758 (Victor: roof panel 'just for hvac', 7 ACs)unmapped unknownSource: capture #10: Taji's 10/1 AC-to-breaker results (chat.db 944159) not recordedNo running reading in the energy log (inrush only); 3.2 kW = median of the five measured units
Tesla Wall Connector (EV charger)exterior-west24011.533rodco-2024-sub factSource: ~/trc-electrical/source/files/2024-09-29-lighting-contractor-invoice-54.pdf p.1 sub panel line: 'Breakers for existing circuit and car charger'rodco-2024-sub.ev-charger factSource: ~/trc-electrical/source/files/2024-09-29-lighting-contractor-invoice-54.pdf p.1 'new dedicated circuit for car charger'; rating 60 A is inference (~/electrical-plan/taji.html step 2)Measured 11.533 kW (TaskRabbit) and 11.3 kW (Greg); 11.53 kW / 240 V = 48 A implies a 60 A circuit; current cap set lower in Nov/Dec 2025 to an unrecorded value
Sauna heatersauna-review2406.192rodco-2024-sub inferenceSource: ~/trc-electrical/source/files/2024-09-29-lighting-contractor-invoice-54.pdf p.1 dedicated sauna circuit billed with the new sub panel; panel not statedrodco-2024-sub.sauna inferenceSource: ~/trc-electrical/source/files/2024-09-29-lighting-contractor-invoice-54.pdf p.1 'new dedicated circuit for sauna plug in alley'Energy log 'Spa/Cold Plunge' 6.192 kW listed as inrush; a resistive heater has no inrush, so this is read as heater running draw (inference). No nameplate; inventory MISC351 Aleko heater may be a spare
Cold plunge chiller and pumpsauna-review1200.8unmapped unknownSource: no source names the panel or breaker for this loadunmapped unknownSource: no source names the panel or breaker for this load104.4 W measured after 1 min (likely pump or idle); 0.8 kW is a typical 1/2 to 3/4 HP chiller compressor running
Water heater (existence unknown)kitchenNoneunmapped unknownSource: no source names the panel or breaker for this loadunmapped unknownSource: no source names the panel or breaker for this loadInspector found no water heater; kitchen has a hot/cold water tower; no Rheem/AO Smith/Navien/Rinnai/tankless hit in any swept folder
Main refrigerator (replaced 10/2024)kitchen1200.15unmapped unknownSource: Farzad rewired gym and kitchen outlet circuits to 'the outdoor panel' in Nov 2025 (texts-ari-electrical.txt:514-517); which kitchen outlets is not recordedunmapped unknownSource: Farzad rewired gym and kitchen outlet circuits to 'the outdoor panel' in Nov 2025 (texts-ari-electrical.txt:514-517); which kitchen outlets is not recordedTypical full-size fridge 0.15 kW running, ~1 kW start; 110 V per Farzad; no model
Dishwasher (replaced 10/2024)kitchen1201.5unmapped unknownSource: Farzad rewired gym and kitchen outlet circuits to 'the outdoor panel' in Nov 2025 (texts-ari-electrical.txt:514-517); which kitchen outlets is not recordedunmapped unknownSource: Farzad rewired gym and kitchen outlet circuits to 'the outdoor panel' in Nov 2025 (texts-ari-electrical.txt:514-517); which kitchen outlets is not recordedTypical residential dishwasher heater 1.2-1.8 kW during wash and dry; no model
Range / oven (electric, 220 V)kitchen2403.0unmapped unknownSource: Farzad rewired gym and kitchen outlet circuits to 'the outdoor panel' in Nov 2025 (texts-ari-electrical.txt:514-517); which kitchen outlets is not recordedunmapped unknownSource: Farzad rewired gym and kitchen outlet circuits to 'the outdoor panel' in Nov 2025 (texts-ari-electrical.txt:514-517); which kitchen outlets is not recordedFarzad lists the oven as 220 V, so electric; 3 kW = one element or oven bake average; connected nameplate likely 8-12 kW
Espresso machinekitchen1201.5unmapped unknownSource: Farzad rewired gym and kitchen outlet circuits to 'the outdoor panel' in Nov 2025 (texts-ari-electrical.txt:514-517); which kitchen outlets is not recordedunmapped unknownSource: Farzad rewired gym and kitchen outlet circuits to 'the outdoor panel' in Nov 2025 (texts-ari-electrical.txt:514-517); which kitchen outlets is not recordedStandby 13 W measured; 1.5 kW typical boiler element; no model
Coffee machinekitchen1201.0unmapped unknownSource: Farzad rewired gym and kitchen outlet circuits to 'the outdoor panel' in Nov 2025 (texts-ari-electrical.txt:514-517); which kitchen outlets is not recordedunmapped unknownSource: Farzad rewired gym and kitchen outlet circuits to 'the outdoor panel' in Nov 2025 (texts-ari-electrical.txt:514-517); which kitchen outlets is not recordedStandby 13 W measured; 1.0 kW typical brewer element; no model
Microwavekitchen1201.5unmapped unknownSource: Farzad rewired gym and kitchen outlet circuits to 'the outdoor panel' in Nov 2025 (texts-ari-electrical.txt:514-517); which kitchen outlets is not recordedunmapped unknownSource: Farzad rewired gym and kitchen outlet circuits to 'the outdoor panel' in Nov 2025 (texts-ari-electrical.txt:514-517); which kitchen outlets is not recordedStandby 13 W measured; 1.5 kW input for a ~1,000 W unit
Hot/cold water towerkitchen1200.5unmapped unknownSource: Farzad rewired gym and kitchen outlet circuits to 'the outdoor panel' in Nov 2025 (texts-ari-electrical.txt:514-517); which kitchen outlets is not recordedunmapped unknownSource: Farzad rewired gym and kitchen outlet circuits to 'the outdoor panel' in Nov 2025 (texts-ari-electrical.txt:514-517); which kitchen outlets is not recordedTypical dispenser 420-500 W heater plus ~100 W cooler
Kitchen small plug loads (water filter, Roborock vacuum, air purifier)kitchen1200.1unmapped unknownSource: Farzad rewired gym and kitchen outlet circuits to 'the outdoor panel' in Nov 2025 (texts-ari-electrical.txt:514-517); which kitchen outlets is not recordedunmapped unknownSource: Farzad rewired gym and kitchen outlet circuits to 'the outdoor panel' in Nov 2025 (texts-ari-electrical.txt:514-517); which kitchen outlets is not recordedThree items at 13 W each measured; peak adds vacuum dock charging
Mini fridge (Lounge)bar-lounge1200.044unmapped unknownSource: no source names the panel or breaker for this loadunmapped unknownSource: no source names the panel or breaker for this loadMeasured 44 W running; start surge ~0.6 kW typical (SCE named mini fridges a spike culprit); other mini fridges uncounted
Lounge small loads (fan 24 W, Alexa, Apple speakers) and Lounge TVbar-lounge1200.2unmapped unknownSource: Lounge TV and speakers sit on the rain-trip breaker (chat.db 936762, register unplaced.rain-trip); its panel is not identifiedunmapped unknownSource: Lounge TV and speakers sit on the rain-trip breaker (chat.db 936762, register unplaced.rain-trip); its panel is not identifiedMeasured fan 24.1 + Alexa 1.3 + speakers 10.5 + 5 = 41 W; Lounge TV unmeasured, ~0.15 kW typical
Mezzanine small loads (Alexa, Natural Sound AV receiver)mezzanine-review1200.15unmapped unknownSource: no source names the panel or breaker for this loadunmapped unknownSource: no source names the panel or breaker for this loadMeasured 3.1 W idle; receiver under program ~0.15 kW typical
Clothes dryer (electric, dedicated 2024 circuit)exterior-west2405.0rodco-2024-sub inferenceSource: ~/trc-electrical/source/files/2024-09-29-lighting-contractor-invoice-54.pdf p.1 dedicated dryer circuit billed with the new sub panel; panel not statedrodco-2024-sub.dryer inferenceSource: ~/trc-electrical/source/files/2024-09-29-lighting-contractor-invoice-54.pdf p.1 'new dedicated circuit for dryer plug in alley'Dryer has a dedicated 2024 RodCo circuit and is listed 220 V by Farzad; 5 kW typical element; machine location unrecorded (circuit at the alley wall)
Clothes washerexterior-west1200.5unmapped unknownSource: no source names the panel or breaker for this loadunmapped unknownSource: no source names the panel or breaker for this load110 V per Farzad; 0.5 kW typical motor; location unrecorded
IYO LED wall, 49 x DW1.9 SPro cabinets, NovaStar VX600studio-a-live120 presumed3.15unmapped unknownSource: breaker routing requested from Farzad 9/16 (chat.db 940199), no answer recorded (register unplaced.led-wall)unmapped unknownSource: breaker routing requested from Farzad 9/16 (chat.db 940199), no answer recorded (register unplaced.led-wall)Spec sheet max 307 W/m2, average 103 W/m2 x ~10.25 m2 = 3.15 kW max, 1.06 kW average (duty 0.35 = avg/max); standby 0.2 kW receiving cards (inferred)
Live Room stage lighting rig (truss fixtures via stage distro)studio-a-live120 (distro on 2 of 3 phases)2.0sqd-outdoor-stage inferenceSource: ~/trc-electrical/source/email/2026-08-13-insurance-inspection-rec-photos.pdf p.4 (report p.23) breaker label STAGE LIGHTSsqd-outdoor-stage.stage-lights inferenceSource: ~/trc-electrical/source/email/2026-08-13-insurance-inspection-rec-photos.pdf p.4 photo 2, 100 A STAGE LIGHTS; the rig's own distro feed is not tracedIf installed: 5 x Intimidator Spot 360X at 217 W (manual) + 8 x EVE TF-20 at 24 W + pars/FX ~0.5 kW = ~1.8 kW; inventory shows most fixtures in storage, so the hung set is unknown
House and room lighting, building-wide (track, LED, dimmers)main-circulation1202.0unmapped unknownSource: staff switch 'the lighting breaker' off at night (chat.db 938079); which panel and which lights is not identifiedunmapped unknownSource: staff switch 'the lighting breaker' off at night (chat.db 938079); which panel and which lights is not identified4,883 sq ft at ~0.4 W/sq ft LED, with 1995 track lighting in control, iso, recording, rehearsal, office; no fixture schedule exists
Outdoor string lightspatio-review1200.013sqd-outdoor-stage inferenceSource: ~/trc-electrical/source/email/2026-08-13-insurance-inspection-rec-photos.pdf p.4 breaker label OUTDOOR; chat.db 942453-942457 'outside breaker' for the lightsunmapped unknownSource: two OUTDOOR breakers; which one feeds the string lights is not recorded (capture #6)Measured 13 W
Trident 88 console power supplies (PMI 1 and PMI 2)studio-a-control1200.239ch-console inferenceSource: ~/trc-electrical/source/imessage/2026-08-03-handoff-imgD-subpanel-console.png labels 'Console #1-#5'; ~/trc-electrical/out/plans-electrical-findings.md:501 reads it as the 1995 tech-power panelunmapped unknownSource: five 'Console' labels; which feeds the Trident PSUs is not recorded (capture #5)Measured 118.1 + 120.5 W; linear console supplies draw near-constant
Mixing Room outboard racks: Manley pre and ELOP+, Demeter, 2 x Drawmer 1968, 2 x AEA TAP3, 2 x Antelope Orion, Crown amp, Trinnov, Mac minimachine-racks1200.25unmapped unknownSource: no source names the panel or breaker for this loadunmapped unknownSource: no source names the panel or breaker for this loadMeasured sum 199.6 W (each under 50 W); peak adds Crown amp under program
Mixing Room monitoring and room loads: Antelope L/R, Kali and small subs, PSI AVAA, Hear Back hub, Viotek monitor, wash and Recording Club lights, lava lamp, chargersstudio-a-control1200.35unmapped unknownSource: no source names the panel or breaker for this loadunmapped unknownSource: no source names the panel or breaker for this loadMeasured sum 251.6 W (each under 50 W); peak allows program level on powered monitors
Mixing Room TCL TVstudio-a-control1200.053unmapped unknownSource: no source names the panel or breaker for this loadunmapped unknownSource: no source names the panel or breaker for this loadMeasured 53.2 W
Live Room FOH: Allen & Heath SQ-7, 2 Samsung monitors, dummy Mac mini, grandMA3, Dell lighting PCstudio-a-live1200.29unmapped unknownSource: no source names the panel or breaker for this loadunmapped unknownSource: no source names the panel or breaker for this loadMeasured SQ-7 60.3 + Dell 75.2 + monitors 54.6 + Mac 6.9 + grandMA3 12.3 = 209 W; peak uses SQ-7 manual 110 W
Live Room PA and monitors: 6 x QSC K wedges, 2 x Kali subs, Linea Research Xib4 ampstudio-a-live1201.2unmapped unknownSource: no source names the panel or breaker for this loadunmapped unknownSource: no source names the panel or breaker for this loadIdle measured 6 x 35.7 + 2 x 17 = 248 W; peak: QSC K 1.9 A at 120 V each (manual) at 1/2 program plus Xib4 (4 x 1,250 W rated) at ~1/8 power
Live Room video: 6 x Blackmagic Studio 6K cameras, ATEM Television Studio HD8 ISO, NovaStar TU20 Pro, 252 W TVstudio-a-live1200.5unmapped unknownSource: no source names the panel or breaker for this loadunmapped unknownSource: no source names the panel or breaker for this loadMeasured cameras 6 x 30.7 + ATEM 40.9 + TU20 14.7 + TV 252 = 492 W
Mic closet: Allen & Heath GX4816 stage box, Hear Back units, Catapult RX (passive)mic-closet1200.1unmapped unknownSource: no source names the panel or breaker for this loadunmapped unknownSource: no source names the panel or breaker for this loadGX4816 manual max 80 W; Hear Back units PoE-fed
Rehearsal Room PA and backline: Midas board, 2 stage boxes, Turbosound mains and subs, Fender guitar and bass amps, Mark Bass, keyboards, IEM receivers, computerrehearsal-room1200.9unmapped unknownSource: no source names the panel or breaker for this loadunmapped unknownSource: no source names the panel or breaker for this loadIdle measured sum 380 W (each under 50 W); peak inferred for amps and powered speakers at program level, Midas manual 120 W
Rehearsal Room main lights 197 W, wash lights 47.7 W, Insignia TV 86.3 Wrehearsal-room1200.331unmapped unknownSource: no source names the panel or breaker for this loadunmapped unknownSource: no source names the panel or breaker for this loadMeasured sum 331 W
Recording Room: big light 72 W, Primacoustic L/R, sub, Alexa; backline unmeasuredrecording-room1200.4unmapped unknownSource: no source names the panel or breaker for this loadunmapped unknownSource: no source names the panel or breaker for this loadMeasured 108 W; peak adds amps/keys in session (unmeasured)
Podcast Room: ATEM 42.8 W, cameras 3 and 4, 2 Insignia TVs, AITOE, HA400, Alexapodcast-room1200.2unmapped unknownSource: no source names the panel or breaker for this loadunmapped unknownSource: no source names the panel or breaker for this loadMeasured sum 145.6 W (each under 50 W)
Office: Lorex 16-channel NVR plus PoE cameras, printer, chargers, office computers and monitorsoffice-machine1200.4unmapped unknownSource: no source names the panel or breaker for this loadunmapped unknownSource: no source names the panel or breaker for this loadMeasured printer/USB/battery 14 W each; NVR + 16 PoE cameras ~0.12 kW typical; laptops/monitors ~0.2 kW
Network core: Frontier modem/router, PoE switch(es) for lighting, Hear Back, NAS, PTZ; NAS; camera relayselectrical-room1200.3unmapped unknownSource: no source names the panel or breaker for this loadunmapped unknownSource: no source names the panel or breaker for this load48-port PoE switch ~50 W base plus PoE load, NAS ~40 W, modem/router ~20 W; models unrecorded